OptiMate
Series
Back
to the OptiMate Index page 
Back
to the OM600 Index page 
OptiMate® OM640
Module with Dark Gray Enclosure
 |
|
The OM640 Operator Panel
is a low cost/high performance man/machine interface with a
broad range of operator input and display capabilities. The
terminal includes a 4 line by 20 character LCD display, five
function keys, 3 LED light bar indicator lamps, and the capability
to display text messages, BCD, BCD Double, Binary and Floating
Point numbers. |
OptiMate® configuration software allows you to predefine
up to 160 messages. These messages can be later selected by your
PLC or computer program to display status, variable data and allow
numeric data input. For computer applications, additional messages
can be sent directly over the serial communication port.
Function keys and indicator lamps can be custom labeled
by the user with plastic inserts. The inserts can be custom legended
with text and/or graphics, and slipped into protective pockets behind
the faceplate.
The OM640 Operator Terminal is part of Optimation's
OptiMate® series. Each OptiMate® module is designed to connect to
a microprocessor or to most PLC's with a single cable connection.
OptiMate® modules can be used individually, or together with any
combination of other OptiMate® modules.
When used with a microprocessor system, simple communications
over either an RS232 or RS422 communications cable allows the microprocessor
to directly control the lights and LCD display as well as to read
function key status.
When used with a PLC, operation is transparent to
the user. Terminal functions tie directly into your PLC ladder logic
program. The OM640 takes care of the rest.
Features 
.
4 line x 20 character backlit LCD display
. 3 LED light bar indicator lamps
. 5 tactile snap pushbuttons - independently
configurable for momentary or       alternate
action mode
. User-Legendable function keys and indicator
lamps
. 160 User-definable messages
. Stand alone capability
with direct connection to most PLCs
. Compatible with any computer via
serial communications
. Mix and match with other OptiMate®
modules
Benefits 
.
Eliminates the need for controller I/O modules for operator panel
use
. Easy function selection, display and status
indication in one module
. Reduces system integration and retrofit
costs
. Remove and replace maintainability
. Rapid future expansion
. Reduced maintenance costs
. Attractive, eye-appealing
appearance
Operational Overview
The OM640 Panel incorporates all of the basic elements necessary
for operator interface. Function keys allow operator function selection,
and the alphanumeric display provides text information.
The OM640 interfaces over either an RS232 or RS422
serial link to any computer-based system and many popular PLCs.
In a computer-based system, interface occurs via a very easy to
use OptiMate® Hex protocol. For a PLC-based system, operation is
totally controlled through a bank of 14 PLC registers. Everything
else is handled by the OM640 terminal.
PLC Based Systems
PLC-based systems access the OM640 via a bank of 14 registers. Buttons
appear as coils and contacts (or register bits) in the PLC. Messages
can be predefined, stored in the OM640 and used by the PLC program.
To use a predefined message, your PLC program simply places the
message number that you have associated with the message into a
PLC register. Text, data display, and arrow adjustment messages
are all available. Up to 160 messages can be predefined.
There are three types of messages that handle numeric
values. A data display message will display the value you place
in the line's data register in the message field that has been predefined.
The top display line on the right illustrates a data display message.
The message has been predefined as message # 6. The carets(^) in
the message are place holders for the numeric display. To use the
message to display data, simply place the value '6' in the top line
message select register and the value (in this case, 64197324) in
the top line data register(s). The OM640 takes care of the rest.
Use With a Computer
The OM640 Panel provides all of the same capabilities to a computer-based
system that it does to PLC systems. It also provides the added capability
to utilize additional messages that are not predefined, but passed
over the serial link. The OptiMate® Hex protocol makes computer-based
applications a very simple undertaking. To control the lamps or
LCD display, simply send the appropriate message over the serial
link. Upon receiving the appropriate message, the OM640 will respond
with the button status.
Specifications 
Physical
.
Recessed Mount Housing 6.6"L x 4.0"H x 1.25"D
. Cutout size for above 3.55"Hx5.80"L
. Panel Fasteners : Four, 6x32 threaded
studs, (on ends, symmetrical about     center line)
. Weight : 12 ounces
. Color: Dark gray
housing.
. Function keys
: White with user-supplied label
. Lamp colors available:
Red, Green, Yellow
. LCD display :
4 line x 20 character STN with LED backlight character size :         4.75mm
high x 2.95mm wide
. Button Type :
Membrane panel with dome switch snap action
Electrical
. Power (all lamps on) : 8 -30VDC @2.04Watts
. 170 mA @ 12VDC
85mA @ 24VDC
. Power connector : Pluggable terminal
block, 2 position
Communications
. RS232 and RS422 ; 4821 to 19200 baud
. Compatible with most major PLC protocols
. Hex Slave Protocol for computer-based systems
. 15 pin female 'D' shell connector
Environmental
. Enclosure - NEMA 4 (installed)
. Temperature - 0 to 50 C
. Humidity - 95% Non-condensing
Labelling of Function keys
. User-defined slide-in Labels
Message Types (160 user-defined
messages available)
. General Text message
. Data display message (one data value per
line)
Numeric Types & Values
. Integer
. Fixed Point
. BCD (Values between 0 & 9999; with appropriate
decimal placement)
. BCD Double (values between 0 & 99999999
with appropriate decimal            
  placement)
. Binary (Values between 0 & 65535 with appropriate
decimal placement)
. Floating Point (Values between -3.402823E+38
to +3.402823E+38 in the       format of ±X.XXE±XX)
OptiMate
Model Series:
|